Extra Heavy-Duty
Pressure Switch

MPSXHD | Installation Guide

Automatic pump start and stop based on system pressure.

Rated for up to 5 HP. Confirm the model and electrical ratings on the label.

Warning | Qualified installer requiredELECTRIC SHOCK, ARC FLASH, EXPLOSION, AND FIRE HAZARD. Incorrect wiring or installation can cause severe injury, death, or property damage. Install and wire only by a qualified person (licensed electrician or trained pump technician) in accordance with NEC (NFPA 70), all applicable local codes, and Merrill instructions. If you are not qualified, contact a professional.

MPSXHD | Product views

MPSXHD | Cover on
MPSXHD | Cover on, with product notes
MPSXHD | Cover off
MPSXHD | Cover off, with product notes

Select either image to open it at full size. Replace the cover before startup.

Before you start

Use the same basic pressure-switch installation procedure. Verify MPSXHD model, voltage/HP ratings, pressure range, tank air charge, and sensing connection. Follow the wiring diagram for the exact switch.

Installation | 4 simple steps

  1. Disconnect power. Relieve pressure.

    A qualified installer locks out the correct breaker, verifies zero voltage, then opens a drain until the gauge reads 0 PSI.

  2. Check the tank and pressure connection.

    Check precharge with the water side drained. Remove sediment from the pressure sensing port; replace damaged or restricted fittings.

  3. Install the pressure switch.

    Use suitable thread sealant on compatible male pipe threads. Keep the pressure opening clear and avoid twisting or damaging the switch housing.

  4. Connect wiring. Replace the cover.

    A qualified installer follows the exact switch markings and model wiring diagram, verifies grounding and ratings, then secures the cover before restoring power.

Operation + safe startup

How the pressure switch works

MPSXHD | Automatic cut-in / cut-out

As system pressure falls to the cut-in setting, the switch closes its contacts to start the pump. When pressure rises to the cut-out setting, the contacts open to stop the pump.

Open contacts are not an electrical disconnect.Always isolate power at the breaker before service.

Pressure settings

MPSXHD models have factory cut-in and cut-out settings such as 30/50, 40/60, 60/80 and 80/100 PSI. Confirm the exact settings and system pressure ratings before use. Only a qualified installer should make adjustments, following the switch instructions.

Startup check | Qualified installer

1 | Restore

Confirm cover is secured. Restore power under qualified supervision.

2 | Observe

Use a working gauge; verify pump starts and stops at the correct pressures.

3 | Stop if

Stop for unsafe pressure, repeat trips or abnormal cycling.

Bladder tank precharge (empty)

Switch settingPrecharge
30/50 PSI28 PSI
40/60 PSI38 PSI
60/80 PSI58 PSI

Stop + call a qualified professionalPump will not stop, no water, rapid cycling, leaks, tripped breaker, overheated wiring or relief-valve discharge. Disconnect power at the breaker and seek qualified service.